Quality control in cable manufacturing covers the sequence of tests and inspections applied from raw material receipt to finished cable shipment. For a buyer evaluating a cable factory, the relevant questions are which tests are performed, at what stage, against which standard, and what records are produced. Cable testing is generally divided into routine tests performed on every production length, sample tests performed on a selection of lengths, and type tests performed on a design to verify its performance. Routine tests typically include conductor resistance measurement, insulation resistance measurement, and voltage withstand testing. Additional tests such as partial discharge, flame spread, smoke density, and halogen content apply depending on the cable type and the standards referenced. This page describes the testing sequence and documentation practices at our factory so that buyers can compare them against their project requirements.
02 Company Profile
Jiangsu Qucheng Cable Technology Co., Ltd., established in 2018, operates a 40,000-square-meter factory in Yixing, Jiangsu. Our testing center is equipped for conductor resistance, insulation resistance, voltage withstand, partial discharge, flame spread, smoke density, and halogen content testing, and our production process is monitored through a 5G-based smart manufacturing system that records extrusion and curing parameters for each production run. We hold ISO9001, ISO14001, and ISO45001 management system certifications, along with CB and TÜV product qualifications. Buyers evaluating our factory can request the test equipment list and sample test reports as part of their supplier assessment.
03 Application Fields
- Supplier Supplier qualification - Factory assessments by utilities, EPC contractors, and distributors comparing test capability and documentation.
- Project Project acceptance - Documentation packages submitted for infrastructure and grid project acceptance.
- Tender Tender submission - Test reports and certificates attached to technical bids for cable supply contracts.
- Audit Third-party audits - Factory audits by certification bodies and customer representatives.
- Complaint Failure investigation - Test records used to trace and investigate field failures or quality complaints.
04 Technical Specifications
| Routine Tests | Conductor resistance, insulation resistance, voltage withstand on every production length |
| Sample Tests | Dimensions, insulation thickness, mechanical properties on selected lengths |
| Type Tests | Partial discharge, flame spread, smoke density, halogen content, thermal tests on design samples |
| Partial Discharge | ≤ 10 pC at 1.5 U₀ for medium-voltage cables |
| Flame Testing | IEC 60332-1-2 single cable; IEC 60332-3-24 bunched cables |
| Smoke Density | IEC 61034, light transmittance ≥ 60% for LSZH cables |
| Halogen Content | IEC 60754-2, pH ≥ 4.3, conductivity ≤ 10 µS/mm |
| Records | Batch numbers on cable linked to production and test records |
| Traceability | Raw material certificates, production parameters, and test results per batch |
| Standards | IEC 60502-1, IEC 60502-2, IEC 60227, IEC 60332, IEC 61034, IEC 60754 |
05 Key Features & Core Characteristics
- Routine Every production length undergoes conductor resistance, insulation resistance, and voltage withstand testing before shipment.
- PD Medium-voltage cables are routine tested for partial discharge at 1.5 U₀ with a 10 pC acceptance limit.
- Fire Flame spread, smoke density, and halogen content testing are performed on the constructions where these properties are specified.
- Digital The 5G-based manufacturing system records extrusion and curing parameters for each run, supporting traceability beyond the final test results.
- Batch Batch numbers printed on the cable link each length to its production record and material certificates.
- Docs Test reports and certificates can be organized into documentation packages for project acceptance and tender submission.
06 Technical Notes
The structure of cable testing follows the standards referenced by the cable type. For low-voltage cables under IEC 60502-1, routine tests are conductor resistance, insulation resistance, and voltage withstand, with sample tests for dimensions and mechanical properties. For medium-voltage cables under IEC 60502-2, partial discharge testing is added to the routine tests, and the acceptance limit of 10 pC at 1.5 U₀ is the commonly applied criterion. Type tests, which verify the design rather than individual lengths, cover items such as bending, thermal cycling, and short-circuit withstand, and are performed once on a representative sample. For flame retardant and LSZH cables, the relevant tests are IEC 60332-1-2 and IEC 60332-3-24 for flame spread, IEC 61034 for smoke density, and IEC 60754-2 for halogen content. Documentation practice matters as much as the tests themselves: a test report that cannot be linked to the delivered cable length has limited value in a dispute or audit. Our batch marking and production records are designed so that any delivered length can be traced back to its material batches and test results. Buyers conducting factory assessments can request the equipment list, calibration records, and sample reports before placing orders.
07 Frequently Asked Questions
Furthermore, the company has integrated a 5G-based smart manufacturing system, enabling digital monitoring of the production process and full quality traceability, thereby enhancing efficiency and product consistency. Qucheng Cable is committed to providing safe, reliable, and high-performance cable solutions for global customers.