An electric wire gauge chart maps nominal conductor area to current capacity, resistance and voltage drop. Electricians, panel builders, purchasers and project engineers use it to move between AWG, mm2 and circular mil without guessing. The result is reliable only when installation method, insulation rating, ambient temperature and run length sit beside it.
A wire gauge chart is a reference table that links conductor size to electrical and thermal limits; it does not replace a code calculation, a termination check or the cable manufacturer data.
An electric wire gauge chart measures conductor size against current capacity, resistance and voltage drop; it does not certify a cable for a specific installation.
Every useful row carries four data points. Missing one turns a chart into a rough guess.
Use the chart to reject unsafe sizes, then confirm the selected conductor against the overcurrent device, terminal rating, grouping factor and voltage-drop limit.
A gauge row is a boundary condition, not a product approval. The same 6 mm2 copper conductor can behave differently in free air, in a conduit bundle and inside a control panel.
AWG, mm2 and circular mil describe the same conductive area in different standards; 10 AWG is about 5.26 mm2, not a separate 10 mm2 cable.
The approximate conversions below are the values to use when a drawing, a supplier catalogue and a terminal datasheet use different size systems.
| Size | Area | 75 C ampacity | Typical check |
| 14 AWG | 2.08 mm2 | 20 A | 15 A branch-circuit limit under NEC 240.4(D) |
| 12 AWG | 3.31 mm2 | 25 A | 20 A branch-circuit limit under NEC 240.4(D) |
| 10 AWG | 5.26 mm2 | 35 A | 30 A branch-circuit limit under NEC 240.4(D) |
| 8 AWG | 8.37 mm2 | 50 A | 40 A to 50 A equipment and subpanels |
| 6 AWG | 13.3 mm2 | 65 A | 50 A to 60 A feeders and equipment |
| 4 AWG | 21.2 mm2 | 85 A | 70 A to 80 A feeders |
| 2 AWG | 33.6 mm2 | 115 A | 100 A service and feeder checks |
| 1/0 AWG | 53.5 mm2 | 150 A | 125 A feeder and distribution checks |
IEC 60228 separates Class 1 solid, Class 2 stranded, Class 5 flexible and Class 6 extra-flexible conductors. The class changes bending radius, termination method and strand count; it does not change the nominal area printed on the chart.
A 2.5 mm2 Class 5 flexible conductor and a 14 AWG solid conductor are not interchangeable in a terminal block. The clamp range, strand size and torque value decide whether the joint is sound.
For fixed low-voltage wiring, the PVC insulated cable range rated 450/750 V applies these metric conductor sizes in a defined product construction.
PVC Insulated Cable Series Rated 450/750 VGeneral-purpose PVC-insulated cables for fixed low-voltage wiring, building lighting, equipment connections, and control circuits, available in defined metric conductor constructions.View Product →Ampacity is the current a conductor can carry continuously under stated installation conditions; a 6 AWG copper conductor rated 65 A in one table can carry less when ambient rises or cables are bundled.
The bar chart below uses copper conductors at 75 C, not more than three current-carrying conductors in a raceway, and a 30 C ambient. It is a comparison aid, not a substitute for NEC 310.16 or IEC 60364-5-52.
A 40 C ambient correction factor of 0.88 turns a 50 A 8 AWG row into 44 A. Four current-carrying conductors in one raceway apply an 80% adjustment under NEC 310.15(C)(1). Apply both before comparing the result with the load.
The number printed beside a gauge is a starting ampacity. The final value is the lowest of the corrected conductor ampacity, the terminal rating and the overcurrent device setting.
For 1 kV distribution projects, the extruded insulated power cable range applies the same conductor logic inside a full cable construction.
Extruded Insulated Power Cable for 1 kV and 3 kV SystemsLow-voltage extrusion-insulated power cable with copper or aluminum conductors for industrial, commercial, residential, and urban distribution installations, including indoor, outdoor, and underground use.View Product →Voltage drop can force a larger gauge than ampacity alone: a 6 mm2 copper cable on a 230 V, 32 A, 30 m single-phase run drops about 7.0 V, or 3.0% at conductor operating temperature, before joints and supply tolerance are added.
For single-phase circuits, use Vdrop = 2 x I x R x L / 1000 with R in mV/A/m and L in metres. For three-phase circuits, replace the 2 with 1.732. The result is the drop in volts; divide by system voltage to get percent.
6 mm2 copper at 32 A is within a 75 C installation table for a three-conductor cable, so the thermal check can look clean.
At 30 m and 230 V, the same cable sits at the 3% lighting limit; a 10 mm2 conductor gives more margin.
IEC 60364-5-52 gives 3% for lighting and 5% for other uses from the origin of the installation. Local code, utility tolerance and equipment input range can tighten those figures. The gauge chart only supplies R; the project supplies the limit.
Where the route is fixed, engineered cable solutions should be checked against the actual installation method before the gauge is locked.
Use the chart in a fixed order: calculate design current, select a provisional conductor size, apply correction factors, check voltage drop, then confirm code and product data.
A 10% ambient correction can remove the margin gained by a one-step gauge increase. Derate first, then decide whether a larger conductor is justified.
The chart is most useful when it is treated as a filter. It removes impossible sizes quickly and leaves two or three candidates for the voltage-drop and termination checks.
Gauge charts mislead when they are read without insulation rating, conductor class, grouping, ambient temperature or termination limits; the failures are thermal, mechanical and code-based rather than arithmetic.
| Condition | What changes | Practical effect |
| 90 C insulation | Higher conductor ampacity is available, but terminals may be rated 75 C | Use the lowest rating in the assembly |
| 4 to 6 current-carrying conductors | 80% adjustment under NEC 310.15(C)(1) | A 50 A row becomes 40 A before ambient correction |
| 40 C ambient | Ambient correction factor applies | A 65 A row can fall below a 60 A load |
| Class 5 flexible conductor | Finer strands and different terminal range | Check clamp, ferrule and torque data |
A 90 C conductor does not make a 90 C termination. The weak point in the circuit is the lowest-rated component, not the conductor insulation.
For a project-specific review, contact the cable team with the route length, installation method, ambient temperature and protective device rating.
The five checks that settle a gauge question are ampacity, voltage drop, ambient correction, grouping and termination rating; a chart that omits any one of them is incomplete.
10 AWG is approximately 5.26 mm2 with a nominal copper area of 5.26 mm2. The nearest common metric size is 6 mm2, which is larger and should not be treated as a direct replacement without a new ampacity and voltage-drop check.
In a 30 C, three-conductor installation, 6 mm2 copper can carry 32 A, but a 30 m 230 V single-phase run sits close to the 3% drop limit. Confirm the terminal rating and apply correction factors; 10 mm2 gives more margin on long runs.
No. A 90 C conductor may have a higher ampacity row, but terminals, enclosures and heat-shrink parts are often limited to 75 C. A 90 C conductor terminated in a 75 C device must be sized on the 75 C column.
Use a verified conversion or the AWG area formula, then round to the next available metric size. Key checks: 8 AWG is 8.37 mm2, 6 AWG is 13.3 mm2 and 4 AWG is 21.2 mm2. For procurement, state the standard, conductor class and nominal area.
The final check is not the chart. It is the installed termination, the approved cable datasheet and the code calculation for the actual route.