Electric Wire Gauge Chart: Ampacity, AWG to mm2, and Cable Sizing Rules

Nov 10,2026
A 32 A charger on a 30 m single-phase run can pass a 6 mm2 copper ampacity check and still fail a 3% voltage-drop limit when the cable is grouped with two other circuits. The gauge chart is the first screen, not the final answer.

An electric wire gauge chart maps nominal conductor area to current capacity, resistance and voltage drop. Electricians, panel builders, purchasers and project engineers use it to move between AWG, mm2 and circular mil without guessing. The result is reliable only when installation method, insulation rating, ambient temperature and run length sit beside it.

Core definition

A wire gauge chart is a reference table that links conductor size to electrical and thermal limits; it does not replace a code calculation, a termination check or the cable manufacturer data.

What an Electric Wire Gauge Chart Measures

An electric wire gauge chart measures conductor size against current capacity, resistance and voltage drop; it does not certify a cable for a specific installation.

Every useful row carries four data points. Missing one turns a chart into a rough guess.

  • Nominal area in mm2 or circular mil, plus the AWG or metric size label.
  • Ampacity at a stated conductor temperature, ambient temperature and installation method.
  • DC or AC resistance per unit length, used for voltage-drop and short-circuit checks.
  • Conductor class under IEC 60228 or strand count under the local standard.
3%
Lighting voltage-drop limit in IEC 60364-5-52
5%
Other-use voltage-drop limit in IEC 60364-5-52
75 C
Common terminal rating used for final ampacity checks

Use the chart to reject unsafe sizes, then confirm the selected conductor against the overcurrent device, terminal rating, grouping factor and voltage-drop limit.

Working rule

A gauge row is a boundary condition, not a product approval. The same 6 mm2 copper conductor can behave differently in free air, in a conduit bundle and inside a control panel.

AWG, mm2 and Circular Mil: Three Labels for One Conductor

AWG, mm2 and circular mil describe the same conductive area in different standards; 10 AWG is about 5.26 mm2, not a separate 10 mm2 cable.

The approximate conversions below are the values to use when a drawing, a supplier catalogue and a terminal datasheet use different size systems.

Approximate copper conductor size, area and 75 C ampacity for common AWG values.
Size Area 75 C ampacity Typical check
14 AWG 2.08 mm2 20 A 15 A branch-circuit limit under NEC 240.4(D)
12 AWG 3.31 mm2 25 A 20 A branch-circuit limit under NEC 240.4(D)
10 AWG 5.26 mm2 35 A 30 A branch-circuit limit under NEC 240.4(D)
8 AWG 8.37 mm2 50 A 40 A to 50 A equipment and subpanels
6 AWG 13.3 mm2 65 A 50 A to 60 A feeders and equipment
4 AWG 21.2 mm2 85 A 70 A to 80 A feeders
2 AWG 33.6 mm2 115 A 100 A service and feeder checks
1/0 AWG 53.5 mm2 150 A 125 A feeder and distribution checks

IEC 60228 separates Class 1 solid, Class 2 stranded, Class 5 flexible and Class 6 extra-flexible conductors. The class changes bending radius, termination method and strand count; it does not change the nominal area printed on the chart.

Termination check

A 2.5 mm2 Class 5 flexible conductor and a 14 AWG solid conductor are not interchangeable in a terminal block. The clamp range, strand size and torque value decide whether the joint is sound.

For fixed low-voltage wiring, the PVC insulated cable range rated 450/750 V applies these metric conductor sizes in a defined product construction.

PVC Insulated Cable Series Rated 450/750 VPVC Insulated Cable Series Rated 450/750 VGeneral-purpose PVC-insulated cables for fixed low-voltage wiring, building lighting, equipment connections, and control circuits, available in defined metric conductor constructions.View Product →

Ampacity Is an Installation Result, Not a Gauge Property

Ampacity is the current a conductor can carry continuously under stated installation conditions; a 6 AWG copper conductor rated 65 A in one table can carry less when ambient rises or cables are bundled.

The bar chart below uses copper conductors at 75 C, not more than three current-carrying conductors in a raceway, and a 30 C ambient. It is a comparison aid, not a substitute for NEC 310.16 or IEC 60364-5-52.

Copper ampacity comparison at 75 C
14 AWG
20 A
12 AWG
25 A
10 AWG
35 A
8 AWG
50 A
6 AWG
65 A
4 AWG
85 A
2 AWG
115 A
1/0 AWG
150 A
Values show relative ampacity; verify the actual table row for insulation, ambient and grouping.

A 40 C ambient correction factor of 0.88 turns a 50 A 8 AWG row into 44 A. Four current-carrying conductors in one raceway apply an 80% adjustment under NEC 310.15(C)(1). Apply both before comparing the result with the load.

Final ampacity

The number printed beside a gauge is a starting ampacity. The final value is the lowest of the corrected conductor ampacity, the terminal rating and the overcurrent device setting.

For 1 kV distribution projects, the extruded insulated power cable range applies the same conductor logic inside a full cable construction.

Extruded Insulated Power Cable for 1 kV and 3 kV SystemsExtruded Insulated Power Cable for 1 kV and 3 kV SystemsLow-voltage extrusion-insulated power cable with copper or aluminum conductors for industrial, commercial, residential, and urban distribution installations, including indoor, outdoor, and underground use.View Product →

Voltage Drop: The Check That Overrides a Clean Ampacity Row

Voltage drop can force a larger gauge than ampacity alone: a 6 mm2 copper cable on a 230 V, 32 A, 30 m single-phase run drops about 7.0 V, or 3.0% at conductor operating temperature, before joints and supply tolerance are added.

For single-phase circuits, use Vdrop = 2 x I x R x L / 1000 with R in mV/A/m and L in metres. For three-phase circuits, replace the 2 with 1.732. The result is the drop in volts; divide by system voltage to get percent.

Ampacity pass

6 mm2 copper at 32 A is within a 75 C installation table for a three-conductor cable, so the thermal check can look clean.

Voltage-drop pass

At 30 m and 230 V, the same cable sits at the 3% lighting limit; a 10 mm2 conductor gives more margin.

IEC 60364-5-52 gives 3% for lighting and 5% for other uses from the origin of the installation. Local code, utility tolerance and equipment input range can tighten those figures. The gauge chart only supplies R; the project supplies the limit.

Long runs fail on volts, not amps. A 10 AWG conductor can pass a 30 A ampacity check and fail a 3% drop check at 45 m on a 230 V circuit.

Where the route is fixed, engineered cable solutions should be checked against the actual installation method before the gauge is locked.

How to Use a Wire Gauge Chart in Five Steps

Use the chart in a fixed order: calculate design current, select a provisional conductor size, apply correction factors, check voltage drop, then confirm code and product data.

  1. Calculate design current from the load, including 125% for continuous duty where NEC 210.19(A)(1) applies.
  2. Pick a provisional size from the correct temperature column, not from the largest number on the page.
  3. Apply ambient, grouping, thermal insulation and enclosure factors before comparing with the protective device.
  4. Run the voltage-drop calculation over the real route length, including final connections.
  5. Verify the terminal clamp range, bending radius, conductor class and cable datasheet.
Sequence matters

A 10% ambient correction can remove the margin gained by a one-step gauge increase. Derate first, then decide whether a larger conductor is justified.

The chart is most useful when it is treated as a filter. It removes impossible sizes quickly and leaves two or three candidates for the voltage-drop and termination checks.

Where Gauge Charts Mislead in Real Projects

Gauge charts mislead when they are read without insulation rating, conductor class, grouping, ambient temperature or termination limits; the failures are thermal, mechanical and code-based rather than arithmetic.

Installation conditions that change the answer from a basic wire gauge chart.
Condition What changes Practical effect
90 C insulation Higher conductor ampacity is available, but terminals may be rated 75 C Use the lowest rating in the assembly
4 to 6 current-carrying conductors 80% adjustment under NEC 310.15(C)(1) A 50 A row becomes 40 A before ambient correction
40 C ambient Ambient correction factor applies A 65 A row can fall below a 60 A load
Class 5 flexible conductor Finer strands and different terminal range Check clamp, ferrule and torque data
Weakest link

A 90 C conductor does not make a 90 C termination. The weak point in the circuit is the lowest-rated component, not the conductor insulation.

For a project-specific review, contact the cable team with the route length, installation method, ambient temperature and protective device rating.

Practical Sizing Questions

The five checks that settle a gauge question are ampacity, voltage drop, ambient correction, grouping and termination rating; a chart that omits any one of them is incomplete.

What size is 10 AWG in mm2?

10 AWG is approximately 5.26 mm2 with a nominal copper area of 5.26 mm2. The nearest common metric size is 6 mm2, which is larger and should not be treated as a direct replacement without a new ampacity and voltage-drop check.

Can a 6 mm2 cable carry 32 A?

In a 30 C, three-conductor installation, 6 mm2 copper can carry 32 A, but a 30 m 230 V single-phase run sits close to the 3% drop limit. Confirm the terminal rating and apply correction factors; 10 mm2 gives more margin on long runs.

Does a higher temperature rating allow a smaller gauge?

No. A 90 C conductor may have a higher ampacity row, but terminals, enclosures and heat-shrink parts are often limited to 75 C. A 90 C conductor terminated in a 75 C device must be sized on the 75 C column.

How do I convert AWG to mm2 without a chart?

Use a verified conversion or the AWG area formula, then round to the next available metric size. Key checks: 8 AWG is 8.37 mm2, 6 AWG is 13.3 mm2 and 4 AWG is 21.2 mm2. For procurement, state the standard, conductor class and nominal area.

Final check

The final check is not the chart. It is the installed termination, the approved cable datasheet and the code calculation for the actual route.