Electric Wire Size: How to Choose Ampacity, Voltage Drop and AWG Conversion

Nov 03,2026

A 30 kW pump drawing 51 A at 400 V passes every check on a 10 mm² cable inside a temperature-controlled switchroom, then nuisance-trips its 50 A breaker after a year because that same cable runs 80 m through a 40 °C ceiling void beside a second circuit. The conductor was never the wrong size on paper. It was the wrong size for the installation.

Three numbers decide every conductor: the design current the load pulls, the current the conductor can carry after derating, and the voltage lost along the run. Ampacity tables, voltage drop arithmetic and installation factors exist to answer those three questions in order, and the smallest standard size that satisfies all of them is the correct electric wire size.

Electric Wire Size Is a Cross-Sectional Area, Not a Diameter

Electric wire size is the nominal cross-sectional area of the conductor metal, stated in square millimetres under IEC 60228 or as an AWG gauge number in North American practice, and it says nothing about the outer diameter of the finished cable.

A 2.5 mm² cable contains 2.5 mm² of copper, not a 2.5 mm diameter. Once PVC insulation and a sheath are applied, the finished cable measures around 4 mm across, which is why size is read from the printed legend rather than measured with calipers at the site gate.

Conductor class changes handling, not capacity. IEC 60228 defines class 1 solid, class 2 stranded and class 5 flexible conductors, and all three must stay below the same maximum DC resistance at 20 °C: 7.41 ohm/km for 2.5 mm², 3.08 ohm/km for 6 mm² and 1.83 ohm/km for 10 mm². A flexible 10 mm² cable therefore carries what a stranded 10 mm² cable carries, while bending through a much tighter radius inside a machine frame.

Voltage class and size are separate declarations. A 450/750 V cable built to IEC 60227 and a 0.6/1 kV cable built to IEC 60502-1 can both be 4 mm², and the lower voltage class does not automatically mean a lower current rating once insulation compound and installation method are compared.

Standard conductor sizes with IEC 60364-5-52 method C ampacity for copper cable with PVC insulation at 30 °C ambient.
Conductor size Conventional AWG equivalent Ampacity, method C, PVC Typical circuit
1.5 mm² 16 AWG 17.5 A Lighting final circuit
2.5 mm² 14 AWG 24 A 16 A socket outlet ring or radial
4 mm² 12 AWG 32 A 32 A single-phase appliance
6 mm² 10 AWG 41 A Three-phase submain to a small panel
10 mm² 8 AWG 57 A 50 A feeder to a distribution board
16 mm² 6 AWG 76 A 63 A feeder, longer runs
PVC Insulated Cable 450/750V and BelowPVC Insulated Cable 450/750V and BelowGeneral-purpose PVC-insulated wiring for building lighting, equipment connections and control circuits, useful when comparing voltage class and size separately.View Product →

The table is a starting point, not an answer. Every value in the third column assumes one circuit, 30 °C air and a defined installation method, and each of those assumptions is a multiplier that moves the number.

Ampacity Sets the Floor, and Derating Moves It

Ampacity is the maximum continuous current a conductor carries without exceeding its insulation temperature limit, and for copper cable with PVC insulation installed in a thermally insulated wall it runs from 17.5 A at 1.5 mm² to 76 A at 16 mm² under IEC 60364-5-52 method C.

17.5 A1.5 mm², method C
24 A2.5 mm², method C
41 A6 mm², method C
76 A16 mm², method C
Current carrying capacity of copper cable, PVC insulation, method C, 30 °C ambient
1.5 mm²
17.5 A
2.5 mm²
24 A
4 mm²
32 A
6 mm²
41 A
10 mm²
57 A
16 mm²
76 A

Correction factors compound, and that is where most oversights survive to commissioning. At 40 °C ambient the PVC factor is 0.87; bundling two circuits applies 0.80; the product 0.70 turns a nominal 57 A conductor into a 39.9 A conductor. The same 10 mm² cable that looked generous beside a 50 A device is now undersized beside a 51 A load.

Voltage Drop Decides More Runs Than Current Carrying Capacity

Voltage drop is the loss produced by conductor resistance and reactance over the length of the run, and the IEC 60364-5-52 guidance of 3% for lighting and 5% for other loads is what long feeders fail on far more often than ampacity.

The three-phase relationship is voltage drop equals 1.732 multiplied by current, by route length in kilometres, by the sum of resistance times power factor and reactance times the reactive component. Resistance comes from the IEC 60228 maximum values at 20 °C, corrected for operating temperature, and reactance is approximately 0.08 ohm/km for multicore cable. Single-phase circuits replace the 1.732 with 2 and double the resistance path through the neutral.

A 30 kW motor at 400 V with a power factor of 0.85 draws 30,000 / (1.732 x 400 x 0.85) = 50.9 A. Over 80 m of 10 mm² copper, the resistive term is 1.732 x 50.9 x 0.08 x 1.83 x 0.85 = 10.97 V and reactance adds 0.3 V, so the total is 11.3 V, or 2.8% of 400 V. Voltage drop passes. The same cable fails ampacity once the 0.70 combined factor applies, because 10 mm² then carries 39.9 A against a 50.9 A load. The next standard size, 16 mm², carries 53.2 A after derating and drops 1.8% over the identical route.

A conductor can pass voltage drop and fail ampacity, or pass ampacity and fail voltage drop on a long feeder. Both checks are mandatory, and neither replaces the other.

How Metric mm² and AWG Sizing Compare

Metric sizing states conductor area directly while AWG states a logarithmic diameter, and three AWG steps roughly halve or double the area, so 10 AWG at 5.26 mm² sits about 12% below 6 mm² at 6.0 mm² rather than equal to it.

IEC and metric practice
  • Area declared in mm², with maximum resistance fixed by IEC 60228.
  • Ampacity taken from IEC 60364-5-52 tables by installation method.
  • Protective conductor sized by IEC 60364-5-54 Table 54.2.
  • Preferred sizes: 1.5, 2.5, 4, 6, 10, 16, 25, 35 mm².
North American practice
  • Gauge number, moving to kcmil above 4/0.
  • Ampacity taken from NEC Table 310.16 at 60, 75 or 90 °C.
  • Equipment grounding conductor from NEC Table 250.122.
  • Preferred sizes: 14, 12, 10, 8, 6, 4, 3, 2 AWG.

Substitution is where mixed specifications go wrong. A 6 mm² conductor carries roughly 6 A more than 10 AWG under the same installation method, so a design converted by gauge number rather than by area loses margin silently and no inspection catches it. Convert through cross-sectional area, then re-run ampacity and voltage drop in the system that governs the site.

Insulation and Conductor Metal Change the Answer at the Same Size

A 6 mm² copper conductor with 90 °C XLPE insulation carries about 48 A under method C where the same copper with 70 °C PVC carries 41 A, so insulation class is worth 17% of capacity before any derating is applied.

That single fact explains most size disputes between a drawing and a delivered reel. A cable selected from a PVC table and supplied as XLPE is conservative. The reverse is an overheating risk wrapped inside a compliant-looking document, and it only shows up as discoloured insulation at a terminal three summers later.

  • Maximum conductor DC resistance at 20 °C, quoted against an IEC 60228 class.
  • Insulation temperature rating plus the ampacity table that rating references.
  • Conductor class and strand count, which set bending radius and termination method.
  • Copper against copper-clad aluminium: clad conductor of the same area carries roughly 61% of copper conductivity, so it cannot meet the 3.08 ohm/km limit for 6 mm² class 2 copper.

Where route length or ambient temperature sits outside the published tables, cable solutions are usually developed around the installation method rather than the conductor alone, and the insulated power cable selection guide covers construction, voltage class and screening in more detail.

Extruded Insulated Power Cable 1kV and 3kVExtruded Insulated Power Cable 1kV and 3kVLow-voltage copper or aluminum power cable for industrial, commercial and distribution installations, relevant when route conditions fall outside published ampacity tables.View Product →

Six Checks Before You Release the Size

The correct size satisfies six checks in sequence, and the smallest standard size that passes all six is the one to specify: design current, protective device, tabulated ampacity, derating, voltage drop and short-circuit withstand.

  1. Calculate design current from the load, using 1.732 for three-phase and 2 for single-phase circuits, with a realistic power factor.
  2. Select a protective device whose rating is at least the design current and no greater than the cable ampacity.
  3. Read the tabulated ampacity for the actual installation method: clipped direct, in conduit, in a wall, buried or in free air.
  4. Multiply by ambient temperature and grouping correction factors to obtain the installed capacity.
  5. Verify voltage drop against 3% for lighting and 5% for other loads from the origin of the installation.
  6. Confirm short-circuit withstand from the let-through energy of the device, and check the protective conductor against IEC 60364-5-54.

Control and instrumentation circuits run the same arithmetic with a different dominant constraint. A 24 V loop carrying 200 mA fails on voltage drop long before it reaches any thermal limit, which is why a 1.5 mm² control core stays common regardless of the current involved.

Plastic Insulated Control Cable for Signal TransmissionPlastic Insulated Control Cable for Signal TransmissionControl cable with optional shielding for DCS/PLC signals and sensor connections, suited to circuits where voltage drop, not thermal current, sets the size.View Product →

What size cable does a 30 kW motor need at 400 V?

50.9 A of design current at 0.85 power factor, which means 16 mm² copper once the 0.70 combined derating factor applies, because 10 mm² drops to 39.9 A. Where ambient air stays at 30 °C with a single circuit, 10 mm² at 57 A passes ampacity and records 2.8% drop over 80 m.

Is 2.5 mm² the same as 14 AWG?

No. 2.5 mm² is 2.5 mm² of copper against 2.08 mm² for 14 AWG, a 20% difference in metal. Under method C the 2.5 mm² conductor carries 24 A, while 14 AWG copper in the NEC 75 °C column is listed at 20 A.

How long can a 6 mm² cable run at 32 A on a 400 V three-phase circuit?

About 129 m at the 5% limit and 77 m at the 3% limit, using 3.08 ohm/km, 0.08 ohm/km reactance and a 0.9 power factor. Ampacity is not the constraint here, since 6 mm² is rated 41 A before derating and the load sits at 32 A.

Must the protective conductor match the phase conductor size?

Up to 16 mm², yes. IEC 60364-5-54 Table 54.2 requires the protective conductor to equal the phase conductor for phase sizes of 16 mm² and below, then 16 mm² for phase sizes between 16 mm² and 35 mm², and half the phase section above that.